Application The digital gas conditioning system ADS has been designed for continuous use so that detailed gas analyses can be carried out at any time. The entire gas conditioning system is equipped with a PLC which is housed in a compact 19”-housing and can be fully integrated into your gas analysis system. It’s compact design ensures that the ADS takes up little space.
Description The Ankersmid digital gas conditioning system is a compact, low maintenance, self monitoring PLC controlled system. It is suitable for variable and continuous operation for most applications.
A touch screen provides a comprehensive desktop with separate pop-up menus to check and control all parts of the conditioning system as well as external devices. The internal PLC controls the internal Peltier cooler, flow sensor, liquid sensor and the several check valves for zero - and calibration gases and optional and external heated sample line and a gas sample probe.
A sample gas diaphragm pump ensures flow to the analyser and will stop in case of an alarm produced by the cooler or the liquid sensor.
A digital flow sensor is integrated and the flow rate can be checked and adjusted on the touch screen.
The dew point is set at 4°C but can be changed at any value between 1°C and 15°C.
A front-panel fine filter is installed and any condensation is continually removed by a peristaltic pump.
Documentation
General terms of delivery 2024 ENG
Algemene leveringsvoorwaarden 2024
Contaminatie verklaring